Installation and Operation ManualFW6000 Fire Alarm Control PanelFW6000 Intelligent Fire Alarm Control Panel (FACP) is the new-generation fire alarm control unit designed by our company for applications in small and medium projects. It is wall-mounted type and has the advantages of powerful function, high reliability and flexible

Featured Products

Installation and Operation Manual

FW6000 Fire Alarm Control Panel


FW6000 Intelligent Fire Alarm Control Panel (FACP) is the new-generation fire alarm control unit designed by our company for applications in small and medium projects. It is wall-mounted type and has the advantages of powerful function, high reliability and flexible configuration. The panel is equipped with a LCD monitor to display all the information on fire alarms, faults and various operations, which can be printed out by the built-in printer. FW6000 is a one-loop control panel with maximum 240 points, which can work together with all FW 3 series field devices.

Note: COM port needs grounding
1,(Monitoring Start Output)HJ: Active NO terminal to Fire alarm routing device (use jumper to switch  
between passive and active), which will close to connect +24V output after started (each points with a
max output current of 100mA)
2,(Monitoring Start Output)SG: Active NO terminal to Sounder Strobe (Both active and passive modes,  
use jumper to switch between passive and active), which will close to connect +24V output after
started (with max output current of 100mA for each direct-start point)
3,BUS: Non-polarity two-wire bus terminal
4,Linkage power supply output: 24VDC(Max output current 1A)
5,Main board power supply input: 220VAC
6,Grounding Terminal: GroundingNon-Polar Industrial Building Use Addressable Fire Notifier Model Alarm Control Panel
 
2.4 Technical Specifications
2.4.1 Power Supply:
AC power: Nominal operation voltage 220VAC (187VAC ~ 242VAC)
Standby Battery: 2 x 12V/12AH
2.4.2 Operating Environment:
Temperature: 0ºC~+40ºC
Relative Humidity: ≤95%, non-condensing
2.4.3 Capacity: One loop with maximum 240 devices
2.4.4 Display: LCD 128×64 lattice graphic
2.4.5 Dimension: (Length ×Width ×Height):330.0mm×130.0mm×400.0mm
2.4.6 Wiring requirement
1,Recommend to use RVS2×1.0MM2 or RVS2×1.5MM twisted wire for CAN communication wire and bus   
wire, while use RVSP2×1.0mm2 at the high interference environment.
2,Not allowed to lay CAN communication wire and telephone line together with bus wire inside the same        
   multi-core cable.


 